BS EN 12845 Guide:
Designing and Specifying Automatic Sprinkler Systems

BS EN 12845 Guide:
Designing and Specifying Automatic Sprinkler Systems

BS EN 12845 is the standard used across the UK and Europe for the design, installation and maintenance of automatic sprinkler systems in commercial and industrial buildings.

This guide explains what the standard covers, where it applies, how it sits alongside BS 9251 and UK Building Regulations, and what it means when specifying BlazeMaster® CPVC pipe and fittings.

 

What Is BS EN 12845

BS EN 12845, Fixed firefighting systems (Automatic sprinkler systems) Design, installation and maintenance, is a European standard published in the UK by the British Standards Institution (BSI.) It sets out requirements for fixed sprinkler systems in buildings and industrial plant, including systems that form part of life safety measures.

The standard covers hazard classification, water supplies, components, installation and testing, maintenance and the extension of existing systems. It also identifies the minimum building construction details needed for a sprinkler system to perform as designed. Water spray and deluge systems are outside its scope.

The current edition is BS EN 12845:2015+A2:2026, which became the active British Standard on 9th April 2026 and supersedes BS EN 12845:2015+A1:2019. Amendment 2 moves pump set requirements into EN 17451 and ESFR and CMSA storage sprinkler design into EN 12845-2. Core design principles are largely unchanged.

 

2015

BS EN 12845:2015

Initial UK edition

2019

BS EN 12845:2015+A1:2019

 Amendment 1

2026

BS EN 12845:2015+A2:2026

Current edition

Where Does BS EN 12845 Apply?

In the UK, BS EN 12845 is generally used for sprinkler systems in non-residential buildings, such as offices, schools, hospitals, hotels, retail units, and industrial and storage premises. It is also used for residential buildings that fall outside the scope of BS 9251.

Design under BS EN 12845 starts with hazard classification. Occupancies are grouped into Light Hazard (LH), Ordinary Hazard (OH1 to OH4), High Hazard Process (HHP) and High Hazard Storage (HHS). The hazard class determines the design density, the area of operation, the water supply and the components that can be used.

Many UK projects are also designed to the LPC Rules for Automatic Sprinkler Installations, which incorporate BS EN 12845 together with supplementary Technical Bulletins. They are often required by building insurers.

 

BS EN 12845 and BS 9251

BS 9251 is the British Standard for sprinkler systems in residential and domestic occupancies, including houses, flats, care homes and student accommodation. BS EN 12845 covers commercial and industrial buildings, and residential buildings outside the scope of BS 9251.

Mixed-use developments often need both standards. A block of flats may be designed to BS 9251, while ground-floor retail units or a basement car park in the same building are designed to BS EN 12845. The design team should agree early which standard applies to each area and where system boundaries sit.

 

BS EN 12845 and UK Regulations

Building Regulations determine when sprinklers are needed. The standards determine how they are designed and installed.

In England, Approved Document B recommends sprinkler systems in new blocks of flats with a storey more than 11m above ground level. In buildings other than dwellings, it links sprinkler provision to design allowances such as larger compartment sizes.

Approved Document B refers to BS 9251 for dwellings and residential buildings, and BS EN 12845 for non-residential buildings.

Wales, Scotland and Northern Ireland set their own thresholds, so requirements should be confirmed with building control at the start of a project.

 

Key Considerations When Designing to BS EN 12845

 

Legal laws legislation stamp (2)

Hazard classification

Confirm the hazard class of each area before design work begins. A change of use, such as converting office space to storage, can change the classification and the pipe materials that are permitted.

Moisture drops

Water supplies

BS EN 12845 sets the type, pressure, flow and duration of the water supply according to hazard class.

BM icon_2-Sprinkler

Pipework & components

Plastic pipework must be approved for sprinkler use and installed within the conditions of its approval. In the UK, this means certification by the Loss Prevention Certification Board (LPCB) to LPS 1260.

Ease of Installation (1)-1

Installation, testing & maintenance

The standard sets out commissioning tests and a schedule of routine inspection and maintenance. Installers should be trained in the pipe system used.

How BS EN 12845 Relates to BlazeMaster® CPVC Specification

BlazeMaster CPVC pipe and fittings are listed by the LPCB and Underwriters Laboratories (UL) for light hazard occupancies and ordinary hazard installations as defined in BS EN 12845. They are also approved for all light hazard applications under LPS 1260 and BS 9251.

LPC Technical Bulletin TB227 gives examples of Light Hazard and Ordinary Hazard Group 1 (OH1) occupancies where approved plastic pipe may be used. These include schools, offices, hotels, hospitals, nursing homes, museums, libraries and restaurant dining areas, with kitchens, plant rooms and store rooms excluded in several cases.

On BS EN 12845 projects, BlazeMaster CPVC is used in wet pipe systems. Areas classified above OH1, such as car parks, and dry pipe systems require an alternative pipe material.

Key specification data for BS EN 12845 design:

  • Pipe and fittings from 20 mm to 80 mm are rated for continuous service at 175 psi (1207 kPa) at 65°C
  • The system is suitable for ambient temperatures from 2°C to 65°C
  • Hydraulic calculations use a Hazen-Williams C factor of 150, which the pipe maintains throughout the life of the system

Pipe friction loss is calculated in line with the method set out in BS EN 12845.

 

 

Specifying BlazeMaster® CPVC on BS EN 12845 Projects

The Fire Sprinkler Specification Hub brings together the technical data, approvals and design resources needed to specify BlazeMaster CPVC on BS EN 12845 and BS 9251 projects. Resources include the Orange Book Specification Generator Tool and installation guidance.

For project-specific questions on hazard classification, approvals or system design, contact our technical support team.