Where should BlazeMaster®
Fire Sprinkler Systems be used?
BlazeMaster® CPVC pipe and fittings are Listed by Underwriters
Laboratories, Inc. for use in wet pipe sprinkler systems:
- Light Hazard occupancies as defined in the Standard for
Installation of Fire Sprinkler Systems, NFPA 13.
- Residential occupancies as defined in the Standard for
Installation of Sprinkler Systems in Residential Occupancies
up to Four Stories in Height, NFPA 13R.
- Residential occupancies as defined in the Standard for
Sprinkler Systems in One and Two Family Dwellings and Manufactured
Homes, NFPA 13D.
- Air plenums, as defined by the Installation of Air Conditioning
and Ventilating Systems, NFPA 90A and model mechanical codes.
- Underground Water Pressure Service, NFPA 24.
- System risers in accordance with NPFA 13, 13R and 13D
Top
What are BlazeMaster® products' Listings and approvals?
- UL Listed (UL 1821)
- Can be flush at return air plenums
- Mechanical cut-in tee & crosses concealed with Grinnell
figure 730 fittings
- Mechanical cut-in tee & crosses exposed with Grinnell
figure 730 fittings
- Exposed system risers NFPA 13D, 13R
- Exposed basement NFPA 13D (solid wood joist)
- Extended coverage (exposed)
- 20' spacing on pendent in lieu of 15'
- 18' spacing on sidewall in lieu of 14'
- Use with combustible concealed sprinklers
- Tyco attic sprinkler head (to protect the floor below)
- Tyco attic sprinkler head with wet system piping (feed
main and ridge installation)
- Exposed sidewall sprinkler Listing for exposed pipe
& fittings
- 24' extended coverage sidewall sprinkler, 12" drop,
155° F sprinkler head
- 18' extended coverage sidewall sprinkler, 12" drop,
165° F sprinkler head
- 16' extended coverage sidewall sprinkler, 12" drop,
175° F sprinkler head
- 14' standard coverage sidewall sprinkler, 12" drop,
200° F sprinkler head
- ULC or CUL Listed
- Factory Mutual Approved*
- Factory Mutual Approval exposed
- Factory Mutual Approval above drop-in ceilings
- Factory Mutual Approval exposed w/ Soffi-Steel soffiting
covering system - LPCB Approval
- VdS Approval
- Pressure rated system by Plastics Pipe Institute (PPI)
both pipe and fittings
- Cell class 23547 CPVC pipe
- Cell class 24447 CPVC fittings
- Size available up to 3" in diameter
*as manufacturered by Harvel, IPEX, and Tyco
The above data is based on UL and FM reported Listings and
Approvals as of 11/30/05. Check with UL or FM for future updates
on Listings and Approval enhancements.
Other Differentiation:
- World class CPVC R&D center and technical service support
department
- Problem solving CPVC technical service representatives
- Approved commercial product sold for over 20 years
- Back by over 40 years of CPVC resin and compound manufacturing
experienc
- Inventors of CPVC
- CPVC resin & compound from ISO 9001 mfg. sites (85% of
finished product is resin, 15% other)
- CPVC resin & compound made in United States
- Developed UL approved cut-in procedure
- Chemical compatibility program (ancillary products)
- System tool program
- Pipe exceeds ASTM standards (ID, OD tolerances)
- Universal multi-manufacturer CPVC pipe "Quality Assurance
Program"
- BlazeMaster system requires that all CPVC products are made
of BlazeMaster CPVC - mixing other non-BlazeMaster CPVC products
results in a lowest common denominator system
UL Listing
Top
How can the installed cost
of a BlazeMaster® Fire Sprinkler System be lower than metal
systems?
- BlazeMaster® pipe can be cut on site with a simple hand
tool, eliminating expensive fabrication.
- One-step, solvent cement joining systems keep labor time
to a minimum.
- Pipe and fitting costs are very stable compared to metallics.
Top
What are the advantages of BlazeMaster® Fire Sprinkler
Systems for retrofits?
- Allow for higher occupancy rates during the retrofit.
- The system - pipe, hangers and sprinkler heads - can be
retrofitted quickly, close to the wall, using common hand
tools.
- Easy to install in tight spaces.
- Less mess and less noise mean fewer problems with owners
and occupants.
- New decorative cover systems blend with any décor, are
modular for easy installation, eliminate the need for dropped
ceilings and cover exposed pipes.
- One-step, solvent cement joining systems keep labor time
to a minimum.
Top
How can BlazeMaster® products be combined with
other CPVC products and solvent cements?
All BlazeMaster® pipe, fittings and solvent cement can
be used interchangeably regardless of the licensee that manufactures
the products. These combinations have been evaluated and are
included in the UL Listing of BlazeMaster® products.
The BlazeMaster® products' Listing and approvals does not
include the combination of BlazeMaster® CPVC with other types
of CPVC pipes, fittings and solvent cements. Other manufacturers
may have requested that UL investigate the combination of
their CPVC products with BlazeMaster® CPVC. Questions related
to the Listing and approval limitations of other CPVC products
should be directed to the appropriate agency or the specific
manufacturer. Always request a written response to determine
if the agency has investigated and listed the combination
of non-BlazeMaster® CPVC products with BlazeMaster® CPVC.